Chapter 1 · Lesson 1.3
Low demand, high demand and SIL levels
The reliability level of a SIF is not measured the same way depending on whether it is called on rarely or often. Two operating modes are therefore distinguished, and for each, four SIL levels.
Two modes
Low demand
The function is called on rarely, at most once a year. This is the usual case in the process industry: the drum SIF is only demanded if the gas outlet is blocked.
Quantity used: the PFDavg, the average probability that it fails to respond when demanded.
High demand or continuous mode
The function is called on more than once a year, or acts permanently (stopping a press at each cycle, a brake).
Quantity used: the PFH, the average frequency of dangerous failure per hour.
The four SIL levels
| SIL | Low demand: PFDavg | Risk reduction (1/PFD) | High demand: PFH (per hour) |
|---|---|---|---|
| 4 | from 10-5 to less than 10-4 | more than 10,000 to 100,000 | from 10-9 to less than 10-8 |
| 3 | from 10-4 to less than 10-3 | more than 1,000 to 10,000 | from 10-8 to less than 10-7 |
| 2 | from 10-3 to less than 10-2 | more than 100 to 1,000 | from 10-7 to less than 10-6 |
| 1 | from 10-2 to less than 10-1 | more than 10 to 100 | from 10-6 to less than 10-5 |
Each level corresponds to a factor of 10. A SIL 2 SIF in low demand must therefore respond at least 99 times out of 100 on average; a SIL 3, at least 999 times out of 1,000.
Reaching the right PFDavg is not enough: architectural constraints (minimum redundancy) and a systematic capability (quality of design and development) must also be met. These three conditions are detailed in chapter 5.
SIL belongs to the function
People often speak of a “SIL 2 sensor” or a “SIL 3 valve”. This is a shortcut: a component has failure rates and a capability (it is “usable up to SIL 2” under certain conditions), but it is the complete function, with its architecture, tests and maintenance, that reaches a SIL or not.
In practice, the process industry most often limits its SIFs to SIL 3. A need for SIL 4 is generally a sign that the design should be reviewed or other layers added.
- Low demand (at most once a year): PFDavg; high demand or continuous: PFH.
- Four SILs, a factor of 10 per level: SIL 2 = PFDavg from 10⁻³ to less than 10⁻².
- SIL belongs to the complete function, not to a component.