Chapter 1 · Lesson 1.1
From risk to safety function
A hazardous installation is protected by several successive layers. When a layer is an automatic system that measures, decides and acts, it is called a safety instrumented function. Functional safety is the discipline that ensures such a function will do what is expected of it, with the reliability that was asked of it.
- Tell process control, alarm, safety instrumented function and mechanical protection apart
- Place IEC 61508 and IEC 61511 and know who applies what
- Distinguish low and high demand and know the four SIL levels
- Link the approach to the accidents that motivated it
The running case: a gas separator drum
A (fictional) gas treatment unit includes a separator drum, V-201, which separates liquids from the gas before compression. If the gas outlet is blocked (control valve closed by mistake, plugging), the pressure rises. Beyond the design pressure, the drum may rupture: this is the hazardous event.
Several protections already exist: pressure control, a high-pressure alarm that asks the operator to act, a relief valve. The risk study concludes that a safety instrumented function (SIF) is needed in addition: three pressure transmitters, a safety PLC and two shutdown valves that cut the gas inlet.
The role of barriers, their confidence level and their PFD are presented in the Industrial risks course (lesson 9-5).
This case does not describe any real installation. All its values are example assumptions, fixed once and for all and reused in the chapters, case studies and quizzes.
Vocabulary
| Term | What it means | In the case |
|---|---|---|
| BPCS (basic process control system) | The automation that runs the process: control loops, sequences | The pressure control of the drum |
| Safety function | What must be done to reach or maintain a safe state, facing a specific hazard | Cut the gas inlet if the pressure exceeds a threshold |
| SIF (safety instrumented function) | A safety function performed by instrumentation: sensors, logic, final elements | PT-201 A/B/C, safety PLC, XV-201 A/B |
| SIS (safety instrumented system) | All the hardware and software that performs one or more SIFs | The unit’s safety PLC and all its sensors and valves |
| SIL (safety integrity level) | A reliability class required of a SIF (1 to 4) | SIL 2 for the drum SIF (chapter 2) |
One layer among others
The SIS is not the only protection, and it is not the first. The logical order is to reduce the risk at the source (design), then through control, then through barriers. Functional safety does not replace a safe design: it deals with the risk that remains.
A layer only counts if it is independent of the initiating event and of the other layers. A SIF that uses the same transmitter as the failing control loop protects against nothing: if the transmitter lies, the control loop and the SIF are wrong together.
- A SIF measures, decides and acts to bring the process back to a safe state facing a specific hazard.
- The SIS is one layer among others: it deals with the risk that remains after a safe design.
- A layer only counts if it is independent of the initiating event and of the other layers.